Reference table

DC Voltage Drop Tables and Formula for 12 V, 24 V, and 48 V Systems

Voltage drop, not ampacity, is what usually forces you into bigger wire on a low-voltage system. These tables give the longest run each conductor supports before the drop exceeds your budget, and the formula so you can compute any case they do not cover.

At 120 V, losing 3 volts in the wiring is a rounding error. At 12 V, losing 3 volts is a quarter of your system, and it is the difference between an inverter that runs and an inverter that trips on low-voltage cutoff while the battery is still half full.

This is the single most common reason a small solar system underperforms. The wire is legal, the wire is cool to the touch, the wire is within its ampacity — and the load at the far end is being starved. Ampacity is a safety limit. Voltage drop is a functionality limit. On low-voltage DC runs of any length, voltage drop is almost always the one that decides your wire size.

The formula

For a DC circuit, current flows out on one conductor and back on the other, so the length that matters is twice the distance to the load:

V_drop = 2 × L × I × R

Where L is the one-way run length, I is the current in amps, and R is the conductor resistance per unit length. As a percentage of system voltage:

drop % = (2 × L × I × R) / V_system × 100

Rearranged to answer the question people actually have — how far can I run this wire?

L_max = (drop_fraction × V_system) / (2 × I × R_per_foot)

This is Ohm’s law, not a code rule. It is arithmetic you can check, and every number in the tables below came out of it.

Copper DC resistance (NEC Chapter 9, Table 8)

AWG Ω per 1000 ft Ω per km
14 3.07 10.1
12 1.93 6.34
10 1.21 3.984
8 0.764 2.506
6 0.491 1.608
4 0.308 1.01
2 0.194 0.634
1 0.154 0.505
1/0 0.122 0.399
2/0 0.0967 0.317
4/0 0.0608 0.1996

These are referenced at 75 °C. A conductor running hot has higher resistance and therefore more drop than the table predicts, which is one more reason not to design right at the limit.

How much drop is acceptable?

There is no single answer, and the sources genuinely disagree. Be careful about who is telling you what.

Circuit Limit Who says so Force
Branch circuit to farthest outlet 3% NEC 210.19(A) Informational Note Advisory only
Feeder plus branch circuit combined 5% NEC 210.19(A) Informational Note Advisory only
Critical DC circuits (bilge pumps, nav lights, main feeders) 3% ABYC E-11 Codified in the standard
Non-critical DC circuits (cabin lighting, accessories) 10% ABYC E-11 Codified in the standard
PV array to charge controller ~3% Industry convention Rule of thumb, not code

The NEC’s 3 percent figure is the one everybody quotes and the one most often misrepresented. It appears in an Informational Note, which in NEC language means explanatory material that is not part of the enforceable requirements, unless a local authority having jurisdiction has specifically adopted it. ABYC’s 3 percent and 10 percent criteria, by contrast, are actual criteria within the standard, with published sizing tables to match.

For practical planning on a small off-grid system, a reasonable posture is:

  • 3% or better for anything upstream of the battery, plus the battery-to-inverter run, because losses there come straight off your harvest or your surge capability.
  • 3% for anything that misbehaves at low voltage — inverters, pumps, compressors, anything with a motor or a low-voltage cutoff.
  • Up to 10% is tolerable for simple resistive or well-regulated loads such as LED lighting on a short branch, where the only consequence is slightly dimmer output.

Maximum one-way run length, 3% drop

Read the row for your wire size and the column for your circuit’s current. The number is the longest one-way distance to the load in feet. The tables already account for the return conductor.

12 V system, 3% maximum drop

Wire 5 A 10 A 20 A 30 A 50 A 75 A 100 A
14 AWG 11 5 2 1
12 AWG 18 9 4 3 1
10 AWG 29 14 7 4 2 1
8 AWG 47 23 11 7 4 3 2
6 AWG 73 36 18 12 7 4 3
4 AWG 116 58 29 19 11 7 5
2 AWG 185 92 46 30 18 12 9
1 AWG 233 116 58 38 23 15 11
1/0 AWG 295 147 73 49 29 19 14
2/0 AWG 372 186 93 62 37 24 18
4/0 AWG 592 296 148 98 59 39 29

Look at what this table is telling you. At 12 V and 100 A — a 1200 W inverter at full tilt — even 4/0 cable, which is nearly as thick as your thumb, only reaches 29 feet at 3 percent. This is why inverters are mounted next to batteries and not across the room.

24 V system, 3% maximum drop

Wire 5 A 10 A 20 A 30 A 50 A 75 A 100 A
14 AWG 23 11 5 3 2 1
12 AWG 37 18 9 6 3 2 1
10 AWG 59 29 14 9 5 3 2
8 AWG 94 47 23 15 9 6 4
6 AWG 146 73 36 24 14 9 7
4 AWG 233 116 58 38 23 15 11
2 AWG 371 185 92 61 37 24 18
1 AWG 467 233 116 77 46 31 23
1/0 AWG 590 295 147 98 59 39 29
2/0 AWG 744 372 186 124 74 49 37
4/0 AWG 1184 592 296 197 118 78 59

48 V system, 3% maximum drop

Wire 5 A 10 A 20 A 30 A 50 A 75 A 100 A
14 AWG 46 23 11 7 4 3 2
12 AWG 74 37 18 12 7 4 3
10 AWG 119 59 29 19 11 7 5
8 AWG 188 94 47 31 18 12 9
6 AWG 293 146 73 48 29 19 14
4 AWG 467 233 116 77 46 31 23
2 AWG 742 371 185 123 74 49 37
1 AWG 935 467 233 155 93 62 46
1/0 AWG 1180 590 295 196 118 78 59
2/0 AWG 1489 744 372 248 148 99 74
4/0 AWG 2368 1184 592 394 236 157 118

Maximum one-way run length, 10% drop, 12 V

For non-critical branch circuits where ABYC’s 10 percent allowance applies.

Wire 5 A 10 A 20 A 30 A 50 A 75 A 100 A
14 AWG 39 19 9 6 3 2 1
12 AWG 62 31 15 10 6 4 3
10 AWG 99 49 24 16 9 6 4
8 AWG 157 78 39 26 15 10 7
6 AWG 244 122 61 40 24 16 12
4 AWG 389 194 97 64 38 25 19
2 AWG 618 309 154 103 61 41 30
1 AWG 779 389 194 129 77 51 38
1/0 AWG 983 491 245 163 98 65 49
2/0 AWG 1240 620 310 206 124 82 62
4/0 AWG 1973 986 493 328 197 131 98

Remember that a 10 percent allowance still has to clear the ampacity requirement. Loosening the drop budget never lets you go below the safe current-carrying size.

Worked example, by hand

A 12 V shed system runs an 18 A load 22 feet from the distribution panel. What size wire?

Start with ampacity. 18 A continuous requires the conductor to be rated for at least 18 A after derating; 12 AWG at 25 A (75 °C, NEC) clears it comfortably. So ampacity says 12 AWG.

Now check drop. 12 AWG is 1.93 Ω per 1000 ft, so 0.00193 Ω per foot:

V_drop = 2 × 22 ft × 18 A × 0.00193 Ω/ft = 1.53 V
drop % = 1.53 / 12 × 100 = 12.7%

Nearly 13 percent — well past even the loose 10 percent allowance. Step up and retry with 8 AWG at 0.000764 Ω per foot:

V_drop = 2 × 22 × 18 × 0.000764 = 0.605 V
drop % = 0.605 / 12 × 100 = 5.0%

Better, but still above 3 percent. 6 AWG gives 3.2 percent; 4 AWG gives 2.0 percent.

Ampacity said 12 AWG. Voltage drop says 6 AWG at minimum and 4 AWG if you want margin — three to four sizes larger. That gap is the entire lesson of this page.

Three ways to reduce drop, ranked by effectiveness

Raise the system voltage. Drop percentage scales with the square of voltage for the same delivered power, because doubling voltage halves the current and doubles the reference voltage. A run that fails badly at 12 V may pass comfortably at 24 V with the same wire. This is why 24 V and 48 V dominate above about 1500 W.

Shorten the run. Drop is linear in length. Moving the inverter three feet closer to the battery is free; upsizing 100 feet of 4/0 cable is not.

Increase the wire size. Effective, but the most expensive lever, and it hits diminishing returns as cable becomes hard to bend, hard to terminate, and hard to route.

Limits of these tables

They assume copper, DC, and the resistance values at the 75 °C reference in NEC Chapter 9 Table 8. They do not account for connection and termination resistance, which is real and adds up across crimps, lugs, busbars, fuse holders, and switches. They do not cover aluminum conductors. They do not account for a conductor running hotter than 75 °C, which raises resistance further.

Design with margin. If a calculation lands within a few percent of your limit, take the next size up — the real installation will be worse than the arithmetic.

Sources and further reading

Figures on this page are traceable to the published documents below. Where a standard is referenced, check the edition your local jurisdiction has adopted before relying on it.

  1. NEC Chapter 9, Table 8 — Conductor Properties (DC resistance, uncoated copper)NFPA 70, republished by buildmyowncabin.comResistance values are referenced at 75 °C conductor temperature.
  2. NEC 210.19(A) Informational Note — branch circuit voltage dropNFPA 70, summarized by calcengineer.comThis note is advisory. It is not an enforceable requirement unless a local jurisdiction has adopted it as one.
  3. ABYC E-11 conductor sizing tables for 3% and 10% voltage dropAmerican Boat and Yacht Council, reproduced with permission by BoatHowTo